SPECIFICATIONS:

Part Number: 5009-421
Manufacturer: Woodward
Product Type: Micronet Field Termination Discrete I/O Module
Size: 305 H x 356 W x 152 D mm
Input Power: 18–32 Vdc
Discrete Outputs: 12 relay outputs
Communication Ethernet: 6 10/100BaseT Ports
Operating Temperature: 0 - 40 degree C
Current Draw: 12 VDC at 650 mA
Ports: RS232, RS422
Repair: 3-7 Day
Availability: In Stock
Weight: 1.82 kg
Country of Origin: United States

FUNCTIONAL DESCRIPTION:

5009-421 is a Micronet Field Termination Discrete I/O Module manufactured and designed by Woodward and used in Gas Turbine Control Systems. The 5009FT is a standard off-the-shelf steam turbine control for use on industrial steam turbines used in critical compressor or generator drive applications. This controller is comprised of Woodward’s field-proven MicroNet TMR® hardware platform and standard steam turbine software algorithms and is designed for use in standard OEM turbine packages or by system integrators in turbine upgrade projects. The 5009FT fault-tolerant design allows it to operate with any single point of failure without shutting down the turbine, and its TMR (triple modular redundant) design and hot-swap module capability, allow users to easily make system repairs while the turbine set is online and operating normally. This control’s special PID-to-PID logic allows stable control during normal turbine operation and bumpless control mode transfers during plant upsets, minimizing process over- or undershoot conditions. The 5009FT controller senses turbine speed via passive or active speed probes and controls the steam turbine through actuators connected to the turbine inlet steam valves.

FEATURES:

  • Fault-tolerant I/O handling and processing
  • Latent fault detection on relay outputs
  • Time-stamped alarms and trips
  • Discrete input time-stamp with 1 ms resolution
  • Analog input time-stamp with 5 ms resolution
  • Extensive fault detection and annunciation—including first-out indication
  • Critical speed avoidance (3 speed bands)
  • Auto start sequence (hot & cold starts)
  • Three sensors per critical parameter can be configured
  • Dual speed/load dynamics
  • Zero speed detection with proximity probe down to 0.5 Hz
  • Peak speed indication for overspeed trip
  • Automatic hand valve operation (using first-stage pressure)
  • Independent Modbus communication links
  • Remote analog setpoints for all PIDs

WOC has the largest stock of Woodward Turbine Control System Replacement Parts. We can also repair your faulty boards. We can also supply unused and rebuilt backed-up with a warranty. Our team of experts is available round the clock to support your OEM needs. Our team of experts at WOC is happy to assist you with any of your automation requirements. For pricing and availability on any parts and repairs, kindly get in touch with our team by phone or email.

FREQUENTLY ASKED QUESTIONS:

What is the Micronet Field Termination Discrete I/O Module?

The Micronet Field Termination Discrete I/O Module is a device designed to facilitate the connection and termination of discrete input and output signals in industrial automation systems.

How is the module installed in the field?

Installation involves connecting the discrete input and output signals to the designated termination points on the module. Ensure proper wiring and follow the installation guide provided by Micronet.

What types of discrete signals does the module support?

The module typically supports various types of digital signals, including binary input and binary output signals.