Part No.: IS200SRLYS1A
Manufacturer: General Electric
Product Type: Simplex Terminal Board
Mounting: DINrail
Size: 15.9 cm high x 17.8 cm wide
Technology: Surface-mount.
Humidity: 5 to 95% non-condensing
Availability: In Stock
Country of Manufacture: United States (USA)
Series: Mark VIe
IS200SRLYS1A is a Simplex Terminal Board developed by GE. It is a part of Mark VIe control system. The SRLY is a simplex S-type terminal board designed to accommodate a PDOA I/O pack. This terminal board stands out for its ability to deliver 12 form C relay output circuits accessible through 48 customer terminals.
World of Controls has the most comprehensive collection of GE Mark VIe components. Please contact WOC as soon as possible if you require any extra information.
What is IS200SRLYS1A?
It is an Simplex Terminal Board developed by GE
What is the purpose of the ID device on terminal board connectors?
Terminal board connectors feature an ID device that stores essential information such as the serial number, board type, revision number, and plug location. This data is crucial for ensuring compatibility and proper functioning within the system.
How does the ID device work with the I/O pack?
The ID device on terminal board connectors is read by the I/O pack. If a mismatch is detected between the information stored on the ID device and the expected parameters, a hardware incompatibility fault is generated, alerting users to potential issues.
Do option boards also have ID devices?
Yes, each option board contains its own ID device, which uniquely identifies the board. This allows for accurate recognition and configuration within the system.
How does the SRLY provide diagnostic feedback?
The SRLY offers diagnostic feedback to the I/O pack by monitoring isolated contacts on each relay position. This enables real-time monitoring and status updates, ensuring efficient operation and troubleshooting.
What additional diagnostic features are available with specific configurations?
When used with WROB, isolated voltage feedback is employed to detect the status of fuse pairs on the board. In the event of an open fuse, a diagnostic is generated. Similarly, when utilized with WROF or WROG, isolated voltage feedback is used to monitor individual fuses. If voltage is present and a fuse is open, a diagnostic is generated.