TECHNICAL SPECIFICATIONS:

Part Number: 5463-336
Manufacturer: Woodward
Series: MicroNet / MicroNet Plus
Module Type: Thermocouple (TC) Input
Number of Channels: 8 Channels
Thermocouple Types: J, K, T, E, R, S, B, N (Software Configurable)
Resolution: 14-Bit
Accuracy: 0.1% of full scale
Cold Junction Compensation: Integrated (on-board)
Isolation: 500 Vdc
Operating Temp: -30 °C to +65 °C
Availability: In Stock
Origin: United States

FUNCTIONAL DESCRIPTION:

The 5463-336 is an 8-Channel Thermocouple Input Module designed for the Woodward MicroNet and MicroNet Plus control platforms. This module provides high-accuracy temperature sensing from a variety of thermocouple types, converting millivolt-level signals into digital values for the system's central processor. It is a critical component for monitoring exhaust gas temperatures (EGT), bearing heat, and combustion chamber conditions in large industrial turbines and engines.

VERSATILE THERMAL INTERFACING

The module is highly flexible, allowing each of its 8 channels to be software-configured for different thermocouple types (such as J, K, or T). It features 14-bit resolution, ensuring that even minor temperature fluctuations are captured with high precision. This granular data is essential for balancing combustion across multiple cylinders or nozzles and for calculating thermal efficiency in real-time.

INTEGRATED COMPENSATION AND NOISE REJECTION

Accurate thermocouple measurement requires precise reference monitoring. The Thermocouple Input Module includes integrated Cold Junction Compensation (CJC) to account for temperature variations at the terminal connection point. Additionally, the module is engineered with 500 Vdc of galvanic isolation and high-order filtering to reject the electrical noise and common-mode interference typically found in turbine-mounted control enclosures.

ADVANCED DIAGNOSTICS AND RELIABILITY

The Thermocouple Input Module is fully integrated into the Woodward self-diagnostic framework, continuously monitoring the integrity of each input loop. The module can detect and report Open Thermocouple (burnout) conditions or internal hardware failures to the CPU immediately. This allows the control system to initiate protective alarms or switch to redundant temperature sensors, preventing equipment damage due to undetected overheating.

WHY BUY FROM WOC:

World of Controls supports your Woodward infrastructure by offering the 5463-336 in both UNUSED and REBUILT conditions. Every thermocouple module is subjected to rigorous calibration and thermal simulation testing on specialized MicroNet test benches to ensure accuracy across all 8 channels. With our global shipping network and dedicated technical support, WOC is your trusted source for maintaining reliable temperature monitoring systems.

FREQUENTLY ASKED QUESTIONS:

What is the Woodward 5463-336?

The 5463-336 is an 8-channel Thermocouple input module used in MicroNet systems to monitor temperatures from various industrial thermocouples.

Which thermocouple types are supported?

The module is software-selectable and supports a wide range of types, including J, K, T, E, R, S, B, and N, making it compatible with almost any industrial temperature probe.

Does the module require external cold junction compensation?

No, the 5463-336 features built-in Cold Junction Compensation, which simplifies wiring and ensures accuracy by measuring the temperature at the input terminals.

How does the module signal a failed sensor?

The module features integrated burnout detection; if a thermocouple wire breaks or the sensor fails open, the module flags an Open Loop fault to the MicroNet CPU for alarm notification.