World Of Controls understands the criticality of your requirement and works towards reducing the lead time as much as possible.
5437-173 - NetCon Field Terminal Module (FTM) is available in stock which ships the same day.
5437-173 - NetCon Field Terminal Module (FTM) comes in UNUSED as well as REBUILT condition.
To avail our best deals for 5437-173 - NetCon Field Terminal Module (FTM), contact us and we will get back to you within 24 hours.
TECHNICAL SPECIFICATIONS
Part Number: 5437-173
Manufacturer: Woodward
Product Type: Field Terminal Module (FTM)
Functional Group: NetCon High-Density Terminal Block Interface
Series: Woodward NetCon System Series
Application: Field Analog Signal Landing & Cable Interfacing
Channel Capacity: Accommodates High-Density Analog Field I/O
Terminal Block Interface: Heavy-Duty Screw-Clamp Barrier Terminals
Cable Connectors: High-Density Multi-Pin Cable Headers for Control Rack Interface
Surge Protection: Integrated Transient Voltage Suppressors & Passive R-C Filters
Shield Terminals: Grounding Bars for Field Cable Shielding
Mounting Style: DIN-Rail / Cabinet Subpanel Mount
Conformal Coating: Yes
System Compatibility: Woodward NetCon Control Systems
Availability: In Stock
Repair Lead Time: 3–7 Days
Country of Origin: United States
Manual Reference: Woodward NetCon System Manual
The Woodward 5437-173 is a NetCon Field Terminal Module (FTM) designed and manufactured by Woodward for the NetCon control system platform. Serving as the physical landing interface between field instrumentation and the main control chassis, the module organizes incoming process signals such as 4–20 mA transmitters, RTDs, and valve position feedback and routes them via multi-conductor cables to internal processing cards.
FIELD SIGNAL LANDING & HIGH-DENSITY TERMINATION:
The primary function of the 5437-173 NetCon FTM is providing structured terminal blocks for field sensor cabling. Heavy-duty screw-clamp connections ensure reliable electrical contact under severe industrial vibration, while multi-pin cable headers allow fast, pre-wired connection to the NetCon VME chassis without individually wiring cables back to the rack.
NOISE FILTRATION & GROUND SHIELD MANAGEMENT:
The Terminal Module integrates passive R-C filter networks and transient voltage suppression devices across input terminals. These onboard components attenuate electromagnetic interference (EMI) and field voltage surges before they can reach control electronics. Integrated grounding rails near the barrier blocks facilitate single-point shield termination for field cables.
WHY BUY FROM WOC
World of Controls maintains the industry's largest inventory of genuine OEM replacement components exclusively for Woodward control systems and turbomachinery governors. To minimize critical plant downtime, we provide both UNUSED surplus and fully REBUILT circuit boards, field terminal modules, and driver cards, each backed by comprehensive warranty protection. Every reconditioned component, including the Woodward 5437-173 NetCon FTM, undergoes rigorous multi-point inspection, terminal continuity verification, and functional bench-testing by our experienced technical team before dispatch. In addition to direct parts supply, our facility offers complete diagnostic repair and unit exchange services with rapid turnaround times for your damaged Woodward hardware. Our dedicated team of automation specialists is available 24/7 to assist with technical selection, live stock verification, and emergency component sourcing for your control panels. Contact us today via phone or email to request pricing, confirm inventory, or arrange fast worldwide shipping.
FREQUENTLY ASKED QUESTIONS:
What is Woodward 5437-173?
The Woodward 5437-173 is a NetCon Field Terminal Module (FTM) used to provide a structured interface between field wiring and the NetCon control system. It provides terminal connections for field analog signals and routes these signals to the control rack through high-density cable connections.
What types of field signals can the 5437-173 interface with?
The Field Terminal Module is designed for high-density analog field I/O connections and can accommodate signals such as 4–20 mA transmitter inputs, RTD signals, and valve position feedback, depending on the connected NetCon system configuration.
How does the Field Terminal Module help reduce electrical noise?
The module incorporates passive R-C filtering and transient voltage suppression components at the field interface. These components help attenuate electrical noise and limit transient disturbances before signals are passed toward the control electronics.
How are field cable shields connected on the Field Terminal Module?
The Field Terminal Module provides grounding bars or shield termination points near the field terminal connections. These points allow cable shields to be terminated in an organized manner and help maintain proper grounding practices within the control cabinet.
What are the common failure symptoms of a Woodward Field Terminal Module?
Possible symptoms include loss or instability of individual field signals, intermittent readings, incorrect analog values, poor terminal continuity, or communication issues between field wiring and the associated NetCon control cards. Troubleshooting should include checking field wiring, terminal connections, cable headers, grounding, and associated control-system circuitry.
How can I troubleshoot a Field Terminal Module with an intermittent field signal?
Inspect the affected terminal for loose wiring, corrosion, damaged screw clamps, or poor cable termination. Check continuity through the associated field circuit and verify the multi-pin cable connection to the control rack. If the external wiring is confirmed to be good, the FTM should be inspected for damaged filtering, surge-protection components, or internal connection faults.